CLIP Notifier 2-loop addressed detection control panel with the following features:

  • Controlled siren output, general alarm and fault relay outputs.
  • Two serial outputs in standard version with two more optional via add-on board. Standard outputs for 16 terminals and pc for download/upload programming
  • Optional outputs for ethernet connection (TCP/IP) and one USB for pc or printer, or one RS232/485 output for connection to NOTI-FIRE-NET
  • Graphic display with 8 lines by 40 columns

Each line allows connection of 99 detectors and 99 modules.

Allows separate management of gas detection, thanks to special interface module, this display must be on a remote terminal dedicated only to technical alarms.

Request info about this product

Notifier 2 loop CLIP fire control panel 99 detectors and modules AM2000N

€1,778.63 Tax included
€1,778.63

Notifier 2 loop CLIP fire control panel 99 detectors and modules AM2000N

€1,778.63
Tax included

-20€

EXTRA

Add the coupon code in the payment page

Limited-time promotion
qty

Notifier 2 loop CLIP fire control panel 99 detectors and modules AM2000N

€1,778.63

Buy it within and receive it from Tuesday, 30 September
Two-year warranty
Secure Payment
Easy return within 14 days

The AM2000N control panel is a microprocessor-based alarm control panel for the management of addressed-type fire-fighting systems developed in accordance with EN-54.2and EN.54.4. EN.54.4 The control panel has 2 loops that manage 99 detectors and 99 modules each, for a total of 198 detectors and 198 input/output interface modules. The control panel is also programmable via PC software (PK2000), which also allows saving of configurations and printing.


Other technical features:

  • Programmable 32-character writings per point and 32 characters per zone
  • 150 geographical zones and 400 groups with logical operators (AND, OR, DEL, etc.)
  • Database of 999 events
  • Auto line programming with dual address recognition
  • Signaling of maintenance needs for detectors
  • CPR certified in accordance with EN 54-2 and EN 54-4 and System Certification EN 54-13
  • 230Vac mains power supply
  • Standard power supply 2.1A
  • 24Vdc auxiliary current of 1A, with resettable and nonresettable output
  • Charging of two 12Vdc 17Ah batteries
  • 1 750mA siren output
  • Dimensions: 483mm x 266mm x 111mm
  • Frequency: 50 / 60 Hz
  • Power consumption: 0.5A
  • Operating temperature: - 5/+ 40° C
  • Relative humidity: 10 ÷ 93 % (non-condensing)
  • Storage temperature: - 10°/+ 50° C
  • Central weight: 6 kg