Urmet reflection smoke detector with max range 100mt

Urmet
UTD 1043/209 8021156026395

Urmet linear reflection smoke detector , with the following features:

  • Supply voltage: 10.8 ÷ 26.8Vdc
  • Idle consumption @24Vdc: 55mA
  • Idle consumption @12Vdc: 45m
  • Consumption in alarm @24Vdc: 50mA
  • Consumption in alarm @12Vdc: 40mA
  • Consumption at fault @24Vdc: 35mA
  • Consumption in fault @12Vdc: 30mA
  • Pre-alarm dimming thresholds: 20%, 25%, 30%, 35%
  • Alarm dimming threshold: 35%
  • Minimum operating distance: 5 meters
  • Maximum operating distance: 100 meters
  • Transmitter beam wavelength: 890nm

Request info about this product

Urmet reflection smoke detector with max range 100mt

€416.65 Tax included
€416.65

Urmet reflection smoke detector with max range 100mt

€416.65
Tax included

-20€

EXTRA

Add the coupon code in the payment page

Limited-time promotion
qty

Urmet reflection smoke detector with max range 100mt

€416.65

Buy it within and receive it from Wednesday, 17 December
klarna Pay in installments with Klarna
Two-year warranty
Easy return within 14 days

The linear smoke detector is particularly suitable for meeting applications in the field of cultural heritage protection, such as: museums, churches, historical buildings, art exhibitions, etc.

Its operating principle is based on the interaction between smoke present in an environment generated by a fire principle and an infrared beam emitted and reflected by a special optical reflector.

Depending on the reflector used, its range of coverage varies.

Other technical features:

  • Beam misalignment tolerance: ±1°
  • Pre-alarm relay 1A, 30Vdc resistive load-NO/NC contact selectable via jumper
  • Alarm relay 1A, 30Vdc resistive load - jumper selectable NO/NC contact
  • Fault relay 1A, 30Vdc resistive load - jumper selectable NO/NC contact
  • Conventional line - input voltage range: 10 to 20Vdc
  • Conventional line - absorption in pre-alarm: 20mA @20Vdc
  • Conventional line - absorption in alarm: 40mA @20Vdc
  • Conventional line - reset pulse duration: 200mS
  • Operating temperature: (-10 ± 3)°C ÷ (55 ± 2)°C
  • Relative humidity: (93 ± 3)%
  • Degree of protection: IP55
  • Dimensions: 248 (W) x 122 (H) x 120 (D) mm