Telemecanique contactor TeSys D 18A 3P 220VAC LC1D18M7

Schneider
SNR LC1D18M7 3389110349504

Telemecanique Schneider LC1D contactor, with the following characteristics:

  • Number of poles: 3
  • Power pole contact composition: 3 NO
  • Control circuit type: AC at "50/60 Hz".
  • Control voltage [Uc]: 220 V "AC" "50/60 Hz".
  • Auxiliary contact composition: 1 NO + 1 NC
  • Rated impulse withstand voltage [Uimp]: 6 kV according to IEC 60947
  • Overvoltage category: Acti9 VigiARC iC40
  • Conventional open air thermal current [Ith]: 10A at <60°C for signaling circuit, 32A at <60°C for power circuit
  • Rated Interrupting Capacity: 300A at 440V for IEC 60947 compliant Power Circuit

Request info about this product

Telemecanique contactor TeSys D 18A 3P 220VAC LC1D18M7

€53.07 Tax included
€53.07

Telemecanique contactor TeSys D 18A 3P 220VAC LC1D18M7

€53.07
Tax included

-20€

EXTRA

Add the coupon code in the payment page

Limited-time promotion
qty

Telemecanique contactor TeSys D 18A 3P 220VAC LC1D18M7

€53.07

Buy it within and receive it from Wednesday, 17 December
klarna Pay in installments with Klarna
Two-year warranty
Easy return within 14 days

Other Features:

  • Average impedance: 2.5 mOhm "50 Hz" - Ith 32A per Power Circuit.
  • Operating time: 12...22 ms closing, 4...19 ms opening
  • Mechanical life: 15 Mccycles
  • Maximum operating speed: 3600 cycles/h at <60 °C
  • Coil technology: without integrated suppressor module
  • Heat dissipation: 2...3 W at 50/60 Hz
  • Auxiliary contacts type: mechanical connection type 1 NO + 1 NC according to IEC 60947-5-1, mirror contact type 1 NC according to IEC 60947-4-1
  • Signaling frequency: 25...400 Hz
  • Minimum switching current: 5 mA per signaling circuit
  • Minimum switching voltage: 17V per signaling circuit
  • Non-overlapping time: 1.5 ms on deactivation between NC and NO contact, 1.5 ms on activation between NC and NO contact
  • Insulation resistance: > 10 MOhm for signaling circuit
  • IP degree of protection: IP20 Front side complies with IEC 60529
  • Climatic sealing: Conforms to IACS E10, conforms to IEC 60947-1 Annex Q category D
  • Treatment of protection: TH in accordance with IEC 60068-2-30
  • Pollution degree: 3
  • Operating ambient temperature: -40/+60 °C, 60/+70 °C with derating
  • Storage temperature: -60/+80 °C
  • Operating altitude: 0...3000 m
  • Fire resistance: 850 °C in accordance with IEC 60695-2-1

Rated operational current [Ie]:

  • 18 A 60 °C) "AC" AC-3 for Power Circuit at <= 440V
  • 32 A 60 °C) "AC" AC-1 for <= 440V power circuit
  • 18 A 60 °C) AC-3e "AC" for power circuit at <= 440V

Motor Power [kW]:

  • 4 kW at 220...230V "AC" "50/60 Hz" (AC-3)
  • 7.5 kW @ 380...400V "AC" "50/60 Hz" (AC-3)
  • 9 kW @ 415...440V 'AC' '50/60Hz' (AC-3)
  • 10 kW @ 500V 'AC' '50/60Hz' (AC-3)
  • 10 kW @ 660...690V 'AC' '50/60 Hz' (AC-3)
  • 4 kW @ 400V 'AC' '50/60Hz' (AC-4)
  • 4 kW @ 220...230V 'AC' '50/60Hz' (AC-3e)
  • 7.5 kW @ 380...400V 'AC' '50/60Hz' (AC-3e)
  • 9 kW @ 415...440V 'AC' '50/60Hz' (AC-3e)
  • 10 kW @ 500V "AC" "50/60 Hz" (AC-3e) 10 kW @ 660...690V "AC" "50/60 Hz" (AC-3e)

Motor Power HP (UL / CSA):

  • 1 hp at 115 V for 1 phase motors "AC" "50/60 Hz"
  • 3 hp at 230/240 V for 1 phase "50/60 Hz" AC motors
  • 5 hp at 200/208 V for 3 phase "50/60 Hz" AC motors
  • 5 hp at 230/240 V for 3 phase "50/60 Hz" AC motors
  • 10 hp at 460/480 V for 3-phase "50/60 Hz" AC motors
  • 15 hp at 575/600 V for 3 phase "50/60 Hz" AC motors

Rated Closing Power Irms:

  • 140 A "AC" for IEC 60947-5-1 compliant signaling circuit
  • 250 A DC for IEC 60947-5-1 compliant signaling circuit
  • 300 A at 440 V for IEC 60947-compliant power circuit

Rated short-time withstand current [Icw]:

  • 145 A at <40 °C - 10 s for Power circuit
  • 240 A @ <40°C - 1 s for Power Circuit
  • 40 A at <40 °C - 10 min for Power Circuit
  • 84 A at <40 °C - 1 min for Power Circuit
  • 100 A - 1 s per signaling circuit
  • 120 A - 500 ms per signaling circuit
  • 140 A - 100 ms per signaling circuit

Associated Fuse Gauge

  • 10 A gG per IEC 60947-5-1 compliant signaling circuit
  • 50 A gG at <= 690 V Type 1 coordination for Power Circuit
  • 35 A gG at <= 690 V Type 2 coordination for Power Circuit

Rated insulation voltage [Ui]:

  • 690 V complying with IEC 60947-4-1 Power Circuit:
  • 600 V CSA certified Power circuit:
  • 600 V UL certified Power circuit:
  • 690 V complying with IEC 60947-1 signaling circuit:
  • 600 V CSA certified Signaling circuit:
  • 600 V UL certified signaling circuit:

Electrical durability:

  • 1.65 Mccycles 18 A AC-3 at Ue <= 440V
  • 1 Mcicli 32 A AC-1 to Ue <= 440V
  • 1.65 Mcicles 18 A AC-3e at Ue <= 440V

Power Dissipation Per Pole

  • 2.5 W AC-1
  • 0.8 W AC-3
  • 0.8 W AC-3e

Connections - terminals

  • Control circuit: Screw terminals 1 cable 1...4 mm²flexible without cable termination
  • Control circuit: screw terminals 2 cables 1...4 mm²flexible without cable termination
  • Control circuit: screw terminals 1 cable 1...4 mm²flexible with cable termination
  • Control circuit: screw terminals 2 wires 1...2.5 mm²flexible with cable termination
  • Control circuit: screw terminals 1 wire 1...4 mm² solid without cable termination
  • Control circuit: screw terminals 2 wires 1...4 mm² solid without cable termination
  • Power circuit: screw terminals 1 cable 1.5...6 mm²flexible without cable termination
  • Power circuit: screw terminals 2 cables 1.5...6 mm²flexible without cable termination
  • Power circuit: screw terminals 1 cable 1...6 mm²flexible with cable termination
  • Power circuit: screw terminals 2 wires 1...4 mm²flexible with cable termination
  • Power circuit: screw terminals 1 cable 1.5...6 mm² solid without cable termination
  • Power circuit: screw terminals 2 wires 1.5...6 mm²solid without cable termination

Tightening torque:

  • Power circuit: 1.7 Nm - on screw terminals - with flat screwdriver Ø 6 mm
  • Power circuit: 1.7 Nm - on screw terminals - with Philips screwdriver No 2
  • Control circuit: 1,7 Nm - on screw terminals - with flat screwdriver Ø 6 mm
  • Control circuit: 1.7 Nm - on screw terminals - with Philips screwdriver No 2
  • Control circuit: 1,7 Nm - on screw terminals - with pozidriv screwdriver No 2
  • Power circuit: 2,5 Nm - on screw terminals - with pozidriv screwdriver No 2

Reliability level safety

  • B10d = 1369863 cycles Contactor with rated load in accordance with EN/ISO 13849-1
  • B10d = 20000000 cycles Contactor with mechanical load according to EN/ISO 13849-1

Control circuit voltage limits

  • 0.3...0.6 Uc -40...70 °C "AC" de-energizing 50/60 Hz
  • 0.8...1.1 Vac -40...60 °C Operating AC 50 Hz
  • 0.85...1.1 Uc -40...60 °C operating "AC" 60 Hz
  • 1...1.1 Uc 60...70 °C operating "AC" 50/60 Hz

Inrush power in VA

  • 70 VA 60 Hz 0.75 20 °C)
  • 70 VA "50 Hz" 0.75 20 °C)


Holding power consumption VA

  • 7.5 VA 60 Hz 0.3 20 °C)
  • 7 VA "50 Hz" 0.3 20 °C)

Mechanical robustness:

  • Open contactor vibration: 2 Gn, 5...300 Hz
  • Closed contactor vibrations: 4 Gn, 5...300 Hz
  • Open contactor shocks: 10 Gn per 11 ms
  • Closed contactor shocks: 15 Gn per 11 ms

Dimensions and weight:

  • height 77 mm
  • Width 45 mm
  • depth 86 mm
  • Weight 0,33 kg

Data sheet

Type:
Contactors