Schneider Circuit Breaker Without Trip ComPacT NSX160F 36kA 4P 160A C16F4

Schneider
SNR C16F4 3606481999818

Schneider basic frame switch ComPacT NSX160F without trip with the following characteristics:

  • Performance level F 36 kA 415 V "AC"
  • Number of poles: 4
  • Rated current: 160A
  • Rated operating voltage: 690V AC 50/60 Hz in accordance with IEC 60947-2
  • Rated insulation voltage: 800V AC 50/60 Hz complying with IEC 60947-2
  • Rated impulse withstand voltage: 8 kV complying with IEC 60947-2
  • Pollution degree: 3 complying with IEC 60664-1: IP protection degree: IP40 complying with IEC 60529
  • IK degree of protection: IK07 complying with IEC 62262
  • Ambient air temperature for operation: -25/+70 degrees
  • Ambient air temperature for storage: -50/+85 degrees

Request info about this product

Schneider Circuit Breaker Without Trip ComPacT NSX160F 36kA 4P 160A C16F4

€503.72 Tax included
€503.72

Schneider Circuit Breaker Without Trip ComPacT NSX160F 36kA 4P 160A C16F4

€503.72
Tax included

-20€

EXTRA

Add the coupon code in the payment page

Limited-time promotion
qty

Schneider Circuit Breaker Without Trip ComPacT NSX160F 36kA 4P 160A C16F4

€503.72

Buy it within and receive it from Thursday, 13 November
klarna Pay in installments with Klarna
Two-year warranty
Easy return within 14 days

Schneider Electric unmistakable green style for the entire ComPacT range:

  • Estimated 40% reduction in wiring time for panel builders
  • Experience easier installation with new ergonomic front plate design
  • Get confidence that all auxiliaries are in the right place and check that you have the right coil rating
  • New ergonomic lever for easy manual switch operation

Maximum rated short-circuit breaking capacity:

  • 10 kA at 600 V AC 50/60 Hz complying with UL 508 - 85 kA at 240 V AC 50/60 Hz complying with UL 508
  • 22 kA Icu at 525 V AC 50/60 Hz complying with IEC 60947-2
  • 35 kA Icu at 440 V AC 50/60 Hz complying with IEC 60947-2
  • 36 kA Icu at 380/415 V AC 50/60 Hz complying with IEC 60947-2
  • 8 kA Icu at 660/690 V AC 50/60 Hz complying with IEC 60947-2
  • 85 kA Icu at 220/240 V AC 50/60 Hz complying with IEC 60947-2
  • 35 kA at 480 V AC 50/60 Hz complying with UL 508
  • 30 kA Icu at 500 V AC 50/60 Hz complying with IEC 60947-2

Rated short-circuit service breaking capacity:

  • 35 kA at 440 V AC 50/60 Hz complying with IEC 60947-2
  • 36 kA at 380/415 V AC 50/60 Hz complying with IEC 60947-2
  • 85 kA at 220/240 V AC 50/60 Hz complying with IEC 60947 -2
  • 22 kA at 525 V AC 50/60 Hz complying with IEC 60947-2
  • 30 kA at 500 V AC 50/60 Hz complying with IEC 60947-2
  • 8 kA at 660/690 V AC 50/60 Hz complying with IEC 60947 -2

Electrical durability:

  • 40000 cycles 440 V AC 50/60 Hz In/2 complying with IEC 60947-2
  • 15000 cycles 690 V AC 50/60 Hz In/2 complying with IEC 60947-2
  • 20000 cycles 440 V AC 50/60 Hz In complying with IEC 60947 -2
  • 7500 cycles 690 V AC 50/60 Hz Compliant with IEC 60947-2

Other Specifications:

  • Performance level: F 36 kA 415 V AC
  • Mounting mode: Fixed
  • Mounting bracket Back plate
  • Elevation connection: Front
  • Negative connection: Front
  • Connection pitch: 35 mm
  • Mechanical durability: 40000 cycles in accordance with IEC 60947-2
  • Dimensions: height 161mm - width 140mm - depth 86 mm

Data sheet

Type:
Switches
Poles:
4P
Power:
36KA
Amps:
160A